Installation Review
This example shows a clean installation.
All wires exit the console and immediately enter a rigid conduit (not shown).In addition, the console has not been altered in any way; unused knock-outs have been left in place and the divider plates have not been removed (each module is physically separated with a metal plate).
This example shows an incorrect installation.
The divider plate was removed between the two USM modules, in slots 2 and 3. This is against Veeder-Root’s installation requirements and violates the UL/cUL and other licensing bodies. The divider plate must remain in place and cannot be modified.
All wires must be run through rigid conduit and can only be used in the module slot that the conduit is connected to.
Further Information
- Contact Veeder-Root Technical Support at +1.800.323.1799 for additional help or questions.
-