The first true solution for phase separation monitoring

The Phase-Two Separation Float Detector provides you with early detection and continuous monitoring of in-tank phase separation and delivers alarms to your Veeder-Root Automatic Tank Gauge to help prevent the pumping of phase separation product into your fueling system.

The earliest detection of phase separation available

The Phase-Two Float offers the earliest possible detection of phase separation, saving money and reputations. The Phase-Two uses multiple densities to detect both water and phase separation in any gasoline storage tank containing up to 15% ethanol, making sure you’re protected under all circumstances.

The Phase-Two float kit replaces the traditional gasoline float kit and is compatible with existing Veeder-Root automatic tank gauges. The float kit also works in pure gasoline with better performance for water detection than existing float kits by having a lower minimum detectable water height, allowing station owners to quickly respond to a potential problem. 

Product Form

Product Number

Description

Notes

886100-000

Phase-Two Float Kit with 5’ cable

UL

886100-010

Phase-Two Float Kit with 10’ cable

UL

886100-020

Phase-Two Float Kit with 20’ cable

UL

Key Features

  • Handles multiple densities. Float able to detect both water and phase separation 

  • Delivers alarms and alerts. Provides continuous monitoring of in-tank phase separation and delivers alarms to your Veeder-Root automatic tank gauge

  • Protects from every angle. Offers you the assurance that your equipment is secure and your inventory and reputation are safe

  • Improved minimum water detection - even in pure gasoline

  • Provides early detection. Provides you with the earliest detection of phase separation available and continuous monitoring to your console

  • Offers simple replacement. The Phase-Two float kit replaces the traditional gasoline float kit.

  • Use in any gasoline storage tank containing up to 15% ethanol. 

Specifications

Fuel Compatibility

All gasoline blends up to 15% ethanol (E15)

Minimum Detection Limit Fuel

7.0 inches

Minimum Detection Limit Water

0.38 inches

Accuracy in Water

± 0.10"

Accuracy in Phase Separation

± 0.75"

Tank Opening

4”

Console Compatibility

TLS-450PLUS, TLS-350 / 300

Probes

Veeder-Root Mag Plus (Type = Mag7-9)