Specifications | Liquid Level Logger LTE CAT-M1/NB-IoT/2G & Ultrasonic Exi Sensor |
Ultrasonic Range 1 | >12cm to 4.7” to 157” at +20°C (-4°F) |
Ultrasonic Resolution | ±0.4” / ±1cm |
Ultrasonic Positioning Requirements | No obstacles within 74° of ultrasonic sensor aperture |
Accuracy | Typically ±0.78” from 4.7” to 118” / ±2cm from 12cm to 3m |
Battery Life 2 | Up to 10 years |
Manual Activation | Magnetically activated reed switch / Audible buzzer |
Altitude Range | <2Km/1.25miles above sea level |
Battery Technology /strong> | 3.6V Lithium Thionyl Chloride Exi “Bobbin type” construction |
Power Requirements | Battery pack with standard cell sizes connected with a 2-wire harness included |
Communication | LTE CAT-M1 or NB-IoT or 2G |
Radio Frequency (Modem Dependent) | BG96 | LTE FDD (Cat M1 & Cat NB1): B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B26/B2
LTE TDD (Cat M1): B39
LTE TDD (Cat M1): B39 EGPRS: 850/900/1800/1900MHz |
BG95 | LTE FDD (Cat M1): B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B25/B26/B27/B28/B66/B85 LTE FDD (Cat NB2): B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B25/B28/B66/B71/B85 EGPRS: 850/900/1800/1900MHz |
GNSS (GPS) (Modem Dependent) | BG96 | GPS, GLONASS, BeiDou/Compass, Galileo, QZSS |
BG95 | GPS, GLONASS, BeiDou, Galileo, QZSS |
Humidity | 0-100% RH |
Operating Temperature | -20°C to +55°C / -4°F to +131°F |
Storage Temperature | 0°C to +30°C / +32°F to +86°F |
Environmental Protection | IP68 – Outdoors |
Material Compatibility | Suitable for use in tanks for the storage of water diesel fuel, kerosene, oil types A2,C1,C2 and D as defined by BS2869 |
Software Features | Nominal +/-4mm @ 2m range |
Tank Mounting Options | Sensor fits directly into 1 ¼”, 1 ½” or 2” BSP existing tank connection |
RoHS 2 Directive (2011/65/EU) & Delegated Directive RoHS 3 (EU) 2015/863 | This Directive lays down rules on the restriction of the use of hazardous substances in electrical and electronic equipment (EEE) with a view to contributing to the protection of human health and the environment, including the environmentally sound recovery and disposal of waste EEE |
Reach Compliance | ICES-003 Issue 6 Class B Digital Apparatus emissions requirement (Canada) CFR 47 FCC Part 15 Subpart B Class B emissions requirements (USA) |
FCC Compliance | ICES-003 Issue 6 Class B Digital Apparatus emissions requirement (Canada) CFR 47 FCC Part 15 Subpart B Class B emissions requirements (USA) |