Stand-Alone Dispenser Pan Sensor
Veeder-Root’s Stand-Alone Dispenser Pan Sensors immediately shut down AC power to the dispenser when fluid is detected in the dispenser pan. Fail-safe design features eliminate the possibility of missing a leak condition.
Easily installed in most dispenser pans and dispenser sumps*, the Stand-Alone Sensors function with most manufacturers’ dispensers. The sensors control and shut down power to the dispenser without the need for additional relays, circuitry or wiring. The sensors’ control interface ensures the intrinsically safe integrity in a Class I Division II hazardous area.
Accurate and reliable, the Stand-Alone Dispenser Pan Sensors withstand the harshest environments.
Stand-Alone Dispenser Pan Sensors are warranted to be free from detects for a period of one year from the date of installation or 15 months from the date of invoice.
Detection Capabilities
Float Switch Dispenser Pan Sensor shuts down dispenser when it detects:
-1-1/2” of liquid at the base of the sensor
Discriminating Dispenser Pan Sensor shuts down dispenser when it detects:
-1/32” of hydrocarbons floating on liquid at any height on the sensor
-1/8” of hydrocarbon liquid at the base of the sensor
-6-1/2” of liquid from the base of the sensor
Operating Capabilities
Operating Temperature Range: 0C to +70C (for freezing liquids); -25C to 70C (for hydrocarbons)
Storage Temperature Range: -40C to 70C
Cable Length: 5 feet
Sensor Dimensions: 11.53” high, 2.13” diameter
Control Interface Dimensions: 9.350” high, 2.17” diameter
Standard Models
| Form No. |
Description |
| 847990-001 |
Dispenser Pan Sensor with Dispenser Control Interface |
| 847990-002 |
Discriminating Dispenser Pan Sensor with Dispenser Control Interface |
| 330020-012 |
Universal Sensor Mounting Kit |
|
| » | Addendum Dispenser Sensors and Containment Sump Sensors for TLS Consoles Installation Manual (577013-724) (PDF)
|
| » | Dispenser Pan Sensors & Containment Sump Sensors Installation Guide (576013-306 Rev F) (PDF)
|
| » | Mag Sump Sensor Installation Guide (577013-812 Rev E) (PDF)
|
| » | Position-Sensitive Pan/Sump Sensor Installation Guide (577013-809 Rev C) (PDF)
|
| » | Stand-Alone Dispenser Pan Sensor with Dispenser Control Interface Installation Manual (576013-845 Rev C) (PDF)
|
| » | Sump Sensor Installation Guide (576013-301 Rev D) (PDF)
|
| » | Liquid-Phase Product Detectors - Results of U.S. E.P.A. Standard Evaluations (576013-917 Rev. B) (PDF)
Products: 847990-001, 847990-002
|
| » | Point Sensor - Liquid Contact Product Detectors - Certification Reports - Results of U.S. E.P.A. Standard Evaluations (576013-864 Rev G) (PDF)
Products: TLS-350, TLS-300, TLS-300i, ILS-350, EMC, EMC BASIC, ProMax, ProPlus, Simplicity
|
| » | Sensor Products - Application Guide (577013-750 Rev K) (PDF)
|
| » | First System Readied for Clean Air Compliance
(March 21, 2003) Petroleum retailers will test to meet California's requirements for complying with the Federal Clean Air Act.
|