Veeder Logo

Overfill Alarm & Acknowledgement Device

Overfill Alarm For use with TLS-350R, TLS-350, TLS-350J, TLS-300, TLS-300C, TLS-300i, TLS-300, ILS-350, and TLS-250 Systems

Veeder-Root's TLS Overfill Alarm provides an early warning of potential tank bulk delivery overfills as required by the Federal regulations governing underground storage tanks. Wired to an alarm relay in a TLS-350R, TLS-350, TLS-350J, TLS-300, TLS-300C, TLS-300i, TLS-300, ILS-350, and TLS-250 or TLS-250i System, the alarm relay activates the TLS overfill alarm horn and light when a potential overfill is detected. All TLS systems have programmable overfill alarm limits that can be set for each tank at a location.

An optional Alarm Acknowledgement Switch is also available for locations where driver intervention is required by local codes. When the driver presses the acknowledgement button, the overfill alarm shuts off and the alarm acknowledgement light illuminates. This light will stay on until the TLS prints an inventory increase report.

A built-in timer lets you adjust length of time that the audible alarm will stay on from 0 to 60 seconds. You can also adjust noise level from 78 to 103dB (at 10 feet).

Features

Enclosure: Painted Steel; NEMA 4; 1/2" conduit connector at bottom of alarm and at left side of acknowledgement switch
Operating Temperature Range: -40 degrees to +150 degrees F
Supply Voltage: 120 VAC, 50/60 Hz

Alarm Unit

Actuation: From TLS alarm contact
Audible Alarm: Output: Adjustable "Time On" from 0 to 60 seconds
Visual Alarm: Lamp Rating - 25 watt, 120 VAC; Lens - Red Polycarbonate; Flashing Rate - 75 per minute
Dimensions: 11" long, 7" wide, 4" deep

Alarm Acknowledgement Switch

Function: Turns off alarm unit while actuating acknowledgement lamp
Acknowledgement Lamp: 120 VAC, amber lens
Dimensions: 7" long, 3" deep

Standard Models

Form No. Description
790091-001 Overfill Alarm
790095-001 Alarm Acknowledgement Switch

Console Compatibility

Console Series
TLS-350R* 8482
TLS-350* 8470
TLS-350-J 8470
TLS-300 8485
TLS-300C 8485
TLS-250 7841
TLS-250i 8485
*Note: An I/O Combination Module (Form No. 329360-001) or a Four-Relay Output Module (Form No. 329359-001) is required for use of the Overfill Alarm and Alarm Acknowledgement Switch with the TLS-350 or TLS-350R system.

   