Mechanical Line Leak Detection
Veeder-Root/Red Jacket industry leading pressurized line leak detection (PLLD) provides environmental compliance without the fuel flow restrictions of mechanical (MLLD) or electronic (ELLD) systems.
Mechanical Leak Detection and Testing
FXV leak detectors are built for superior performance offering the fastest line leak test available for hourly monitoring.
Two models are available: FX1V andFX2V. Both provide fast test times, advanced materials, increased static head capability, and reduced nuisance tripping.
- Guaranteed to detect at a rate of 3 gph at 10 psi for 24 months from
date of manufacture.
- Operates effectively in areas that experience extreme temperature changes.
- Adapts to applications using high-resiliency lines, such as flexible piping.
- Handles up to 11 feet of static head.
- Installs and troubleshoots easily. No special wrenches or tools.
- Handles a variety of fuels including diesel.
Testing
The FX Tester is the ultimate feature of the FXV System, designed to work with its unique "Snap-Tap"connectors. Clean and efficient, the FX Tester is an all-in-one test unit that enables you to test the FX2V mechanical line leak detector, leak detection rate, submersible pump pressure, line resiliency and siphon systems - all performed right at the submersible pump.
The FX Tester performs a variety of tests without spilling product or interrupting business at a dispenser.
FXV leak detectors are UL listed and third party certified to ensure quality performance and durability.