Hydrostatic Sensor
For use with TLS and ILS Systems
Veeder-Root's Hydrostatic Reservoir Sensor accurately detects fluid level change in the reservoir and interstice of a double-wall storage tank. Dual-float and single-float technology models are ideal for locations with high or low water tables.
Available in a dual-float or single-float configuration. The Dual-Float Hydrostatic Sensor is ideal for high groundwater areas, and can differentiate between a high level alarm condition and a low level alarm condition. If an inner-wall leak occurs, the brine solution seeps into the tank lowering the brine level in the reservoir. The Dual-Float Sensor will then trigger a low level alarm. If an outer-wall leak occurs, the groundwater seeps into the reservoir. The dual-float sensor will then triggers a high level alarm.
The Single-float sensor is ideal for low groundwater areas, since it only detects low level alarm conditions. If an inner wall leak occurs, the brine solution seeps into the tank. If an outer-wall leak occurs, the brine solution leaks out of the tank. In both cases, the brine level decreases and the Single-Float Sensor triggers a low level alarm.
This product is designed to meet California's requirement for secondary space monitoring for tanks as required by AB 2481.
Features
Dual-float sensor alarm conditions:
- Leak in inner wall triggers a low level alarm
- Leak in outer wall triggers a high level alarm in high groundwater areas; low level alarm in low groundwater areas
Single-float sensor alarm conditions:
- Leak in inner or outer wall triggers a low level alarm in low groundwater areas
Temperature Rating
Storage: -40 degrees C to + 70 degrees C
Operating: -25 degrees C to +40 degrees C
Rests in salt brine solution of up to 30% calcium chloride
Cable length: 12 feet Single-Float Sensor Dimensions: 6.0" high, 2.5" diameter
Dual-Float Sensor Dimensions: 19.3" high, 2.5" diameter
- Withstands removal from reservoir several times a year without sensor damage
- Clear plastic housing for visual inspection or float operation
Standard Models
| Form No. |
Description |
| 794380-301 |
Single-Float Hydrostatic Reservoir Sensor |
| 794380-303 |
Dual-Float Hydrostatic Reservoir Sensor |
Hydrostatic Reservoir Sensor Console Capability
The Series 7943 Hydrostatic Reservoir Sensor is comparable with the following consoles:
*Note: An Interstitial Sensor Interface Module is required for the use of the Hydrostatic Sensors with the TLS-350 Console.