Veeder-Root's electronic Pressurized Line leak Detection System uses patented measurement technology to test lines at full pump pressure for highly accurate 0.1 gph precision and 3.0 gph gross testing. Plus, two methods of installation give you options that will substantially reduce your costs.
Key Benefits:
- Swiftcheck valve mounts directly into the mechanical line leak detector port
- No need to break product lines
- No sump or manhole reconstruction required for installation
- Ideal for applications where there is no existing sump
- Lower installation and maintenance costs
- Tests lines at full pressure for greater accuracy than other pressure line leak detection systems
- Automatic, precision 0.1 gph testing option eliminates the need for separate annual testing
- Certified to exceed U.S. E.P.A. performance standards
- Supports a wide-range of pump and pipe types; see Veeder-Root Line Leak Application Guide for details
FEATURE | PLLD | WPLLD |
---|---|---|
LINE LEAK DETECTION | ||
3gph Testing | Yes | Yes |
Precision Testing | Optional | Optional* |
Positive Shutdown | Yes | Yes |
3rd Party Certified | Yes | Yes |
INSTALLATION REQUIREMENTS | ||
Requires TLS Console | Yes | Yes |
Installs Without Breaking Piping | Yes | Yes |
Installs Without New Sump | Yes | Yes |
Installs Without New Wires | No | Yes |
*Not Available for flexible piping
Specifications and Compatible Fluids Requirements
The table below lists Veeder-Root Line Leak Detector specifications.
SPECIFICATION | PLLD | WPLLD |
---|---|---|
OPERATING TEMP | -25 TO +130° | -25 TO +130° |
COMPATIBLE FUELS |
UNLEADED GASOLINE |
UNLEADED GASOLINE LEADED GASOLINE 5% METHANOL / 95% UNLEADED 10% ETHANOL / 90% UNLEADED 15% MTBE / 85% UNLEADED DIESEL KEROSENE JET FUEL AVIATION GASOLINE |
LINE FLOW RATE | 120 GPM MAX. W/SWIFTCHECK VALVE | 120 GPM MAX. W/SWIFTCHECK VALVE |
OPERATING RANGE | 0 - 70 PSI | 0 - 70 PSI |
PROOF PRESSURE | 200 PSI | 200 PSI |
MAX. VERTICAL PIPELINE HEIGHT ABOVE TRANSDUCER | 11 FEET |
11 FEET |
MINIMUM PUMP OUTPUT PRESSURE* | 23 PSI | 23 PSI |
*Pump output pressure should be a minimum of 4 PSI above the check valve's relief pressure.
All Veeder-Root Electronic Line Leak Detectors require a TLS-350 or TLS-4XX Console with installed system software versions shown in the table below.
LINE LEAK DETECTOR TYPE | TLS-350 REQUIRED SYSTEM SOFTWARE | TLS-4XX REQUIRED SYSTEM SOFTWARE |
---|---|---|
PLLD | VERSION 7 OR HIGHER | VERSION 1 OR HIGHER |
WPLLD | VERSION 12 OR HIGHER | NOT AVAILABLE |
Veeder-Root recommends that system software for the console be upgraded to the newest version when installing any new hardware. For TLS-350 Consoles, when installing Version 19 software and subsequent releases, PLLD and WPLLD must be specified and customer must upgrade to ECPU2 if not already installed. See Accessories/Upgrades section of price book or your local Veeder-Root authorized distributor for details.