Electronic Line Leak Detection

Electronic Fuel Leak Detection System for Fuel Pumps

Veeder-Root's electronic Pressurized Line leak Detection System uses patented measurement technology to test lines at full pump pressure for highly accurate 0.1 gph precision and 3.0 gph gross testing. Plus, two methods of installation give you options that will substantially reduce your costs.

Key Benefits:

  • Swiftcheck valve mounts directly into the mechanical line leak detector port
  • No need to break product lines
  • No sump or manhole reconstruction required for installation
  • Ideal for applications where there is no existing sump
  • Lower installation and maintenance costs
  • Tests lines at full pressure for greater accuracy than other pressure line leak detection systems
  • Automatic, precision 0.1 gph testing option eliminates the need for separate annual testing
  • Certified to exceed U.S. E.P.A. performance standards
  • Supports a wide-range of pump and pipe types; see Veeder-Root Line Leak Application Guide for details

     
FEATURE PLLD WPLLD
LINE LEAK DETECTION
3gph Testing Yes Yes
Precision Testing Optional Optional*
Positive Shutdown Yes

Yes

3rd Party Certified Yes Yes
INSTALLATION REQUIREMENTS
Requires TLS Console Yes Yes
Installs Without Breaking Piping Yes Yes
Installs Without New Sump Yes Yes
Installs Without New Wires No Yes

*Not Available for flexible piping

 

Specifications and Compatible Fluids Requirements

The table below lists Veeder-Root Line Leak Detector specifications.

SPECIFICATION PLLD WPLLD
OPERATING TEMP -25 TO +130° -25 TO +130°
COMPATIBLE FUELS

UNLEADED GASOLINE
LEADED GASOLINE
5% METHANOL / 95% UNLEADED
0 - 100% ETHANOL
10% ETHANOL / 90% UNLEADED
15% MTBE / 85% UNLEADED
DIESEL
KEROSENE
JET FUEL
AVIATION GASOLINE

UNLEADED GASOLINE
LEADED GASOLINE
5% METHANOL / 95% UNLEADED
10% ETHANOL / 90% UNLEADED
15% MTBE / 85% UNLEADED
DIESEL
KEROSENE
JET FUEL
AVIATION GASOLINE
LINE FLOW RATE 120 GPM MAX. W/SWIFTCHECK VALVE 120 GPM MAX. W/SWIFTCHECK VALVE
OPERATING RANGE 0 - 70 PSI 0 - 70 PSI
PROOF PRESSURE 200 PSI 200 PSI
MAX. VERTICAL PIPELINE HEIGHT ABOVE TRANSDUCER 11 FEET

11 FEET

MINIMUM PUMP OUTPUT PRESSURE* 23 PSI 23 PSI

*Pump output pressure should be a minimum of 4 PSI above the check valve's relief pressure.

All Veeder-Root Electronic Line Leak Detectors require a TLS-350 or TLS-4XX Console with installed system software versions shown in the table below.

LINE LEAK DETECTOR TYPE TLS-350 REQUIRED SYSTEM SOFTWARE TLS-4XX REQUIRED SYSTEM SOFTWARE
PLLD VERSION 7 OR HIGHER VERSION 1 OR HIGHER
WPLLD VERSION 12 OR HIGHER NOT AVAILABLE

Veeder-Root recommends that system software for the console be upgraded to the newest version when installing any new hardware. For TLS-350 Consoles, when installing Version 19 software and subsequent releases, PLLD and WPLLD must be specified and customer must upgrade to ECPU2 if not already installed. See Accessories/Upgrades section of price book or your local Veeder-Root authorized distributor for details.